Programming Your Application 6-7
590 Series DC Digital Converter
ANALOG OUTPUTS
This function block converts the demand percentage into a form suitable for driving the analog
output electronics of the Converter.
Functional Description
Configurable Analog Outputs
INPUT
DIAGNOSTIC
MODULUS
OFFSET
10V CAL
ANOUT 1 (A7)
–
[251] INPUT
–
100.00 %
–
[245] 10V CAL
–
0.00 %
–
[464] OFFSET
–
FALSE
–
[362] MODULUS
–
–
ANOUT 1 (A7) [ 55]
–
0.00V
ANOUT 2 (A8)
–
[252] INPUT
–
100.00%
–
[248] 10V CAL
–
0.00%
–
[465] OFFSET
–
FALSE
–
[363] MODULUS
–
–
ANOUT 2 (A8) [ 56]
–
0.00V
Parameter Descriptions
INPUT
Range: 0 to 499
(SOURCE TAG)
The source Tag No. of the output value.
10V CAL
Range: -300.00% to 300.00%
(% TO GET 10V)
Scaler value which produces 10V output.
OFFSET
Range: -100.00% to 100.00%
Offset value added to the normal output value after the scaler and before the modulus.
MODULUS
Range: TRUE/FALSE
Unsigned analog output enable
ANOUT 1 (A7) to ANOUT 2 (A8)
Refer to the DIAGNOSTICS function block description, page 6-
18.
MMI Menu Map
1
SYSTEM
2
CONFIGURE I/O
3
ANALOG OUTPUTS
4
ANOUT 1 (A7)
4
ANOUT 2 (A8)
% TO GET 10V
MODULUS
OFFSET
SOURCE TAG