6-36 Programming Your Application
590 Series DC Digital Converter
MAIN PORT P1
This function block configures the
Converter to use the plug-in COMMS
Option Board.
MMI Menu Map
1
SERIAL LINKS
2
MAIN PORT P1
SRL LINK ENABLE
GROUP ID (GID)
UNIT ID (UID)
PROTOCOL
BAUD RATE
ESP SUP. (ASCII)
CHANGEBAND (BIN)
ERROR REPORT
PNO.7
OPTION ADDRESS
OPTION VERSION
PARITY
MAIN PORT P1
ENABLED – [146] SRL LINK ENABLE –
0
–
[138] GROUP ID (GID)
–
0
–
[139] UNIT ID (UID)
–
ASCII
–
[148] PROTOCOL
–
9600
–
[150] BAUD RATE
–
DISABLED
–
[152] ESP SUP. (ASCII)
–
0.00%
–
[144] CHANGEBAND (BIN)
–
00C0
–
[158] ERROR REPORT
–
FFF
–
[142] PNO. 7
–
EVEN
–
[334] PARITY
–
0
–
[400] OPTION ADDRESS
–
OPTION VERSION [303]
–
0.00
Parameter Descriptions
SRL LINK ENABLE
Range: ENABLED/DISABLED
Enables port operation.
GROUP ID (GID)
Range: 0 to 7
The Parker SSD Drive's protocol group identity address.
UNIT ID (UID)
Range: 0 to 15
The Parker SSD Drive's protocol unit identity address.
PROTOCOL
Range: See below
Selects the protocol to be used. The selections are:
ASCII
BINARY
OPTION (select OPTION if say a Profibus option is fitted)
BAUD RATE
Range: See below
Selects the Baud Rate.
300
600
1200
2400
4800
9600 (default)
19200
ESP SUP. (ASCII)
Range: ENABLED/DISABLED
Enable if communicating with a unit using Parker SSD Drives' own ESP protocol.
CHANGEBAND (BIN)
Range: 0.00% to 327.67%
Percentage change in value to trigger a BINARY Enquiry Poll update.
ERROR REPORT
Range: 0000 to FFFF
Displays the last error as a hexadecimal code. Writing any value to this parameter will set the
value to >00C0 (No Error). Refer to Chapter 14: “Serial Communications” for a list of codes.
PNO. 7
Range: 0000 to FFFF
Control word for Multi-Parameter Polling (refer to the COMMS Option Board Technical
Manual - Parameter Specification Tables).
PARITY
Range: ODD/EVEN
Selects odd or oven parity.
OPTION ADDRESS
Reserved parameter for use by Parker SSD Drives.
OPTION VERSION
Reserved parameter for use by Parker SSD Drives.