3-40 Installing the Converter
590D DC Digital Converter - HA467078
AC Line Choke Installation Drawing
IMPORTANT: Always use the specified ac line choke with the Converter.
Choke Rating Dimensions (mm) Mtg
Hole
Terminal
Type (DC) A B C C1 D E F G H L W
∅ ∅
CO055192 35A
50µH
50 27.5 130 140 7.5 50 70 155 260
∅7
M8
CO055193 70A
50µH
50 27.5 130 140 7.5 72.5 92.5 155 302.5
∅7
M8
CO055253 110A
50µH
108 85 60 35 160 170 10 76 101 190 341
∅9
M6 I/P & M8
O/P
CO055255 180A
50µH
108 85 60 35 160 170 10 101 127 190 366
∅9
M6 I/P & M8
O/P
CO057960 270A
50µH
110 110 80 60 255 200 40 170 200 280 380
∅13
M8
CO387886 360A
50µH
135 145 80 60 255 200 40 170 200 280 380
∅13 ∅11/∅13
CO057962 550A
25µH
200 157 110 73 306 250 58 189 220 366 398
∅13 ∅13
CO057963 720A
25µH
200 157 110 73 306 250 58 189 220 366 398
∅13 ∅13
For use with EMC filters
CO463036 35A
485µH
108 85 60 35 160 170 10 76 101 190 341
∅9
M8
CO463037 70A
242µH
108 85 60 35 160 170 10 90 116 190 355
∅9
M8
CO463038 110A
154µH
108 85 60 35 160 170 10 102 128 190 367
∅9
M8
CO463039 180A
113µH
108 85 57 37 255 200 40 170 200 280 380
∅13
M6 I/P & M8
O/P
Figure 3-26 Fitting details for the AC Line Choke