Technical Specifications 11-3
590 Series DC Digital Converter
Internal Fuses
PCB Fuses
Board Identification Fuse Rating Parker SSD Drives
Part Number
AH385851 FS1, 5x20mm glass slow-blow (for auxiliary supply,
contactor, fan supply)
3A CH540033
AH385621 FS1, 5x20mm glass slow-blow (for auxiliary supply,
contactor, fan supply)
3A CH540033
AH385128 FS1, 5x20mm glass (fan supply)
FS2, 5x20mm glass (contactor)
FS3, 5x20mm glass slow-blow (auxiliary supply)
1A
3A
400mA
CH460013
CH460033
CH540042
Field Fuses
Identification Fuse Rating Parker SSD Drives
Part Number
10x38mm (all units up to 270A output current) 10A CH430014
10x38mm (all units above 270A output current) 20A CH430024
External Fuses (European)
For fuses where compliance to UL Standards are required, refer to Chapter 12: “Installing the
Converter” - Requirements for UL Compliance.
Product Code BS88 Type Fuse DIN Type Fuse Thyristor A
2
t
Block 2 Fuse Rating Parker SSD Drives
Part Number
Fuse Rating Part Number @ 125
o
C Junction
Temperature
0010 to 0350 35A CH110353 40A CH570044 800 A
2
t
0351 to 0700 75A CH120753 80A CH570084 8,000 A
2
t
0701 to 1100 110A CH120114 160A CH580164 8,000 A
2
t
1101 to 1800 150A CH120154 200A CH580025 15,000 A
2
t
1801 to 2700 300A CH130035 550A CH590554 125,000 A
2
t
2701 to 4500 --- --- 700A CH590075 320,000 A
2
t
4501 to 7200 --- --- 800A CH590085 500,000 A
2
t
Earthing/Safety Details
Earthing Permanent earthing is mandatory on all units because the earth leakage current exceeds 3.5mA
ac/10mA dc under normal operating conditions. Permanent earthing can be laid in two ways::
1. By using a copper conductor of at least 10mm² cross-sectional area.
2. By using a second conductor, through separate terminals electrically parallel to the
protective conductor.
Note: Each conductor itself must meet the local requirements for a protective earth
conductor.
Input Supply Details
(TN) and (IT)
Units with or without external filters are suitable for use on earth referenced (TN) supplies, but
units used with a filter are not recommended for non-earth referenced (IT) supplies..
Earth Leakage Current >50mA (all models)