Parameter Specification Table 10-5
590 Series DC Digital Converter
Tag (MMI) Name Function Block Minimum Value Maximum Value Notes
141 UNIT ID (UID) AUX PORT (P2) 0 15 RW
142 PNO. 7 MAIN PORT (P1) 0 FFFF RW
143 PNO. 7 AUX PORT (P2) 0 FFFF RW
144 CHANGEBAND (BIN) MAIN PORT (P1) 0 32767 RW
145 CHANGEBAND (BIN) AUX PORT (P2) 0 32767 RW
146 SRL LINK ENABLE MAIN PORT (P1) 0 1 RW
147 SRL LINK ENABLE AUX PORT (P2) 0 1 RW
148 PROTOCOL MAIN PORT (P1) 0 1 RW
149 PROTOCOL AUX PORT (P2) 0 1 RW
150 BAUD RATE MAIN PORT (P1) 300 19200 RW
151 BAUD RATE AUX PORT (P2) 300 19200 RW
152 ESP SUP. (ASCII) MAIN PORT (P1) 0 1 RW
153 ESP SUP. (ASCII) AUX PORT (P2) 0 1 RW
154 II RESERVED 0 FFFF RW
155 Serial Link Version Number Unallocated
156 Config info Unallocated
157 Block Length Unallocated
158 ERROR REPORT MAIN PORT (P1) - - RW
159 ERROR REPORT AUX PORT (P2) - - RW
160 Mode N° Unallocated
161 AUX START AUX I/O 0 1 RW
162 MIN MMI CYCLE TM RESERVED 0 65535 RW
163 ILOOP PI MODE RESERVED 0 2 RW
164 TOGGLE PERIOD RESERVED 0 FFFF RW
165 TOGGLE REF 1 RESERVED -30000 30000 RW
166 SEL. INT/CUR/SPD RESERVED 0 4 RW
167 TOGGLE REF 2 RESERVED -30000 30000 RW
168 AUX ENABLE AUX I/O 0 1 RW
169 FIELD ENABLE DIAGNOSTICS 0 1 RO
170 FIELD ENABLE FIELD CONTROL 0 1 RW
171 SETPOINT FLD CURRENT VARS 0 10000 RW
172 INT. GAIN FLD CURRENT VARS 0 10000 RW
173 PROP. GAIN FLD CURRENT VARS 0 10000 RW
174 FLD. WEAK ENABLE FLD WEAK VARS 0 1 RW
175 EMF LEAD FLD WEAK VARS 10 5000 RW
176 EMF LAG FLD WEAK VARS 0 20000 RW
177 EMF GAIN FLD WEAK VARS 0 10000 RW
178 MAX VOLTS FLD WEAK VARS 0 10000 RW
179 MIN FLD CURRENT FLD WEAK VARS 0 10000 RW
180 SPDFBK ALM LEVEL CALIBRATION 0 10000 RW
181 Field Current Feedback Unfiltered Unallocated
182 FIELD I CAL. CALIBRATION 9800 11000 RW
183 FIELD DEMAND DIAGNOSTICS 0 10000 RO
184 FLD.FIRING ANGLE DIAGNOSTICS 0 180 RO
185 FLD QUENCH DELAY FIELD CONTROL 0 6000 RW
186 FLD. QUENCH MODE FIELD CONTROL 0 1 RW
187 5703 INPUT SYSTEM PORT P3 -30000 30000 RW
188 OVER SPEED LEVEL CALIBRATION 0 20000 RW