- PCME STACK 990 MANUAL: 60 -
Use the scroll bar to move the cursor to the required channel.
Press Edit to change sensor to Maintenance Mode.
The following table details the status of various functions according to sensor status:
Sensor Status
Function Enabled Maint Disabled
Emission Alarms
(Control Unit relays
and ROM devices)
Active Inactive Inactive
Comms and Self Test
Alarms
Active Active Inactive
4-20mA and AOM
Outputs
Active Set to 0
Set to 0
Bar Graph Displays Active
Active
(labelled MAINT)
Set to 0
Logging Active
Active
(labelled MAINT)*
Inactive
Alarm Log
-
Maintenance
Alarm
-
*Data may be excluded from Dust Reporter reports.
B
A
C
K
E
D
I
T
Stack 2 Dust MAINT
Stack 3 Dust MAINT
Stack 4 Dust ENABLED
Stack 1 Dust ENABLED
Stack 5 Dust DISABLED