EasyManua.ls Logo

Phoenix Contact AXC F 3152 - PROFINET System Variables

Phoenix Contact AXC F 3152
113 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AXC F X152
76 / 112
PHOENIX CONTACT 107708_en_08
8.12 PROFINET system variables
Table 8-11 lists the PROFINET system variables of the integrated PROFINET controller
functionality.
Table 8-11 PROFINET system variables (PROFINET controller functionality)
System variable Typ e Description
PNIO_SYSTEM_BF BOOL No connection to a configured PROFINET device
An error has occurred in the PROFINET network, i.e., a con-
nection could not be established to at least one configured
PROFINET device. This value is not set if the “Control BF” pa-
rameter was set to FALSE for a PROFINET device. The
PROFINET device has therefore been excluded from con-
nection monitoring.
PNIO_SYSTEM_SF BOOL Diagnostic alarm on a configured PROFINET device
At least one PROFINET device is indicating a system error
(diagnostic alarm or maintenance alarm). The error priority
can be determined from the PNIO_DIAG_AVAILABLE,
PNIO_MAINTENANCE_DEMANDED, and PNIO_MAINTE-
NANCE_REQUIRED variables.
PNIO_MAINTENANCE_DEMANDED BOOL Maintenance demand
At least one PROFINET device is indicating the “maintenance
demand” alarm (high-priority maintenance alarm) with an ac-
tive connection. The PROFINET device can be identified
using the RALRM diagnostic block.
PNIO_MAINTENANCE_REQUIRED BOOL Maintenance required
At least one PROFINET device is indicating the “maintenance
requirement” alarm (low-priority maintenance alarm) with an
active connection. The PROFINET device can be identified
using the RALRM diagnostic block.
PNIO_FORCE_FAILSAFE BOOL All PROFINET devices are prompted to set their configured
substitute values.
If required, the system variable can be written/set from the
program.
PNIO_CONFIG_STATUS WORD Configuration status of the PROFINET controller
PNIO_CONFIG_STATUS_READY BOOL This variable is set if the PROFINET controller has been ini-
tialized correctly. No desired configuration has been loaded
by PLCnext Engineer yet.

Table of Contents

Other manuals for Phoenix Contact AXC F 3152

Related product manuals