POWER ELECTRONICS
DESCRIPTION OF PROGRAMMING PARAMETERS
123
Screen
Description
Default
value
Range
Function
Set
on
RUN
bA.20
Auto tuning
None
0 to 7
NOTE: Comes from the previous page.
OPT.
DESCR.
FUNCTION
6
Tr
Measures the rotor time
constant (Tr) with the
motor in the stopped
position and Control Mode
dr.9 is set to ‘Sensorless’.
7
All PM
The autotuning is activated
for permanent magnet
synchronous motors.
bA.21
Stator
Resistor
0 (*)
(*)
Stator resistor fine setting.
NO
bA.22
Leak
Inductor
0mH (*)
(*)
Leak inductor fine setting.
NO
bA.23
Stator
Inductor
0mH (*)
(*)
Inductor stator fine setting.
NO
bA.24
[3]
Rotor Time
Const
145ms
25 to 5000ms
Rotor time constant fine setting.
NO
bA.25
[3]
Stator
inductance
scale.
100%
50 to 150%
Set stator inductance scale.
NO
bA.26
[3]
Rotor time
constant
scale.
100%
50 to 150%
Set rotor time constant scale.
NO
bA.31
[3]
Regeneration
inductance
scale
80%
70 to 100%
Set regeneration inductance scale.
NO
bA.32
Q-axis
inductance
scale
100%
50 to 100%
Adjust the inductance scale of the reactive
energy axis, Q, for the synchronous motors
permanant magnet motor control.
Note: Visible parameter if dr.9 = PM Sensor-
less
NO
[
3
] These parameters will only be displayed if dr.9 is set to 4 (S-less1).
(*) This value depends on the motor setting.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Power Electronics SD300 Series and is the answer not in the manual?

Power Electronics SD300 Series Specifications

General IconGeneral
BrandPower Electronics
ModelSD300 Series
CategoryInverter
LanguageEnglish

Related product manuals