DESCRIPTION OF PROGRAMMING PARAMETERS
Screen
Description
Default
value
Range
Function
Set on
RUN
AP.31
[32]
Invert PID
N
0: NO
1: YES
Define whether to invert the PID output or
not.
OPT.
FUNCTION
NO
The PID regulator answers in
normal mode. Therefore, when the
feedback value exceeds the
reference signal, it will decrease its
speed. However, if the feedback is
lower than the reference signal
value, the speed will be increased.
SI
The PID regulator answers in
inverse mode. Therefore, when the
feedback exceeds the reference
signal, speed will be increased.
However, when the feedback value
is lower than the reference signal,
the speed will be decreased.
NO
AP.32
[32]
PID output
scale
+100.00
%
0.1 to
1000.0%
Set the PID regulator output magnitude.
NO
AP.34
[32]
PrePID
reference
0.00Hz
0.00 to
dr.20
Set PID controller motion frequency.
Pre-PID function allows configuring the
drive to start at a fixed speed AP.34 until
PID feedback is above the set level (AP.35).
If at a determined moment (AP.36) the drive
does not reach the feedback level set in
AP.35, fault F23 ‘Pipe Fill Flt’ will be
triggered
NO
AP.35
PrePID end
reference
0.0%
0.0 to
100.0%
Set feedback level in PID mode.
NO
AP.36
PrePID delay
600s
0 to
9999s
Set the PrePID time before triggering a
fault F23 ‘Pipe Fill Flt’.
YES
AP.37
Sleep mode
activation
delay
60.0s
0.0 to
999.9s
Set the delay time before enabling the sleep
mode. If the drive operates at a speed value
under the value of AP.38, it will stop running
and enter in sleep mode.
YES