Chapter 5 Function parameter
101
setting and preset
frequency
40
Switch between
frequency source
auxiliary setting and
preset frequency
When the terminal is active, the frequency source
B is replaced with the preset frequency (F0.01)
41
Reserve
42
Reserve
43
PID parameter switching
When DI terminal (E2.19 = 1) is used to switch
PID parameters, if the terminal is invalid, PID
parameters use E2.13 to E2.15; if the terminal is
valid, PID parameters use E2.16 to E2.18
44
Customized definition
fault 1
When fault 1 and fault 2 are active, the inverter
respectively alarms fault Err.27 and fault Err.28,
and deals with them according to the mode
selected by the fault protection action F8.19.
45
Customized definition
fault 2
46
Speed control / torque
control switching
Switch between speed control mode and torque
control mode under vector control mode. If the
terminal is invalid, the inverter will run at the
mode defined by E0.00 (speed/torque control
mode); if the terminal is valid, the inverter will be
switched to another mode.
47
Emergency parking
If the terminal is valid, the inverter will park at the
fastest speed, and the current maintains at the set
upper limit during the parking process. This
function is used to meet the requirements that the
inverter needs to stop as soon as possible when the
system is in a emergency state.
48
External parking terminal
2
In any control mode (keyboard control, terminal
control, communication control), the terminal can
be used to decelerate the inverter until stop, at the
time the deceleration time is fixed for deceleration
time 4.
49
Deceleration DC braking
If the terminal is valid, firstly the inverter
decelerates to the initial frequency of stop DC
braking, and then switches directly to DC braking
status.
50
Clear current running
time
If the terminal is valid, the inverter's current
running time is cleared, the function needs to work
with Timing run (F7.42) and current running time
arrival(F7.45).