Chapter 5 Function parameter
143
When fault self-recovery restart uptime over an hour later, it will restore the original
setting of automatic fault reset.
Fault DO
action
selection
during
automatic
fault reset
If the inverter automatic fault reset function is set, F8.10 can be used to set whether
DO action is active or not during the automatic fault reset
Automatic
fault reset
interval
It is the waiting time from the inverter fault alarm to automatic fault reset.
Overspeed
detection
value
0.00% to 50.0% (maximum
frequency)
This feature is only available when the inverter runs with speed sensor vector control.
When the inverter detects that the actual motor speed exceeds the set frequency, and
the excess is greater than the overspeed detection value(F8.13), and the duration is greater
than the overspeed detection time(F8.14) the inverter will alarm fault ID Err.43, and
troubleshoots according to the protection action.
Detection
value for too
large speed
deviation
0.00% to 50.0% (maximum
frequency)
Detection
time for too
large speed
deviation
This feature is only available when the inverter runs with speed sensor vector control.
When the inverter detects that the actual motor speed is different from the set
frequency, and the deviation is greater than the detection value for too large speed
deviation(F8.15), and the duration is greater than the detection time for too large speed
deviation(F8.16), the inverter will alarm fault ID Err.42, and troubleshoots according to
the protection action.
If the detection time for too large speed deviation is 0.0s, the detection for too large
speed deviation is canceled.
Fault
protection
action
selection 1
Motor overload (Fault
ID Err.11)
Stop at the selected mode