Chapter 5 Function parameter
58
No.
Code
Parameter
name
Setting range
Factory
setting
Chan
ge
Reference
page
256.
F8.00
Overcurrent
stall gain
0 to 100
20
140
257.
F8.01
Overcurrent
stall protection
current
100% to 200%
150%
140
258.
F8.02
Motor overload
protection
selection
0: Disable
1: Enable
1
141
259.
F8.03
Motor overload
protection gain
0.20 to 10.00
1.00
141
260.
F8.04
Motor overload
pre-alarm
coefficient
50% to 100%
80%
141
261.
F8.05
Overvoltage
stall gain
0 to 100
0
141
262.
F8.06
Overvoltage
stall protection
voltage / energy
consumption
brake voltage
120% to 150%
130%
141
263.
F8.07
Input phase loss
protection
selection
Units digit:Input phase loss
protection selection
0: Disable
1:
Enable
Tens digit:contactor
actuation protection
0: Disable
1:
Enable
11
142
264.
F8.08
Output phase
loss protection
selection
0: Disable
1:
Enable
1
142
265.
F8.09
Short to ground
protection
0:
Invalid
1: Valid
1
142