MVI56-PDPMV1 ControlLogix Platform Reference
PROFIBUS DPV1 Master User Manual
Page 245 of 251 ProSoft Technology, Inc.
CIP Message Support
CIP Messaging is supported for mailbox communication and status retrieval.
CIP messaging is executed using a Generic CIP Message instruction using the
Class value of 4 (assembly object). The instance value identifies the data used
by the MSG instruction. The only two service types supported by the module are
Get Attribute Single (0x0E) and Set Attribute Single (0x10). The Class parameter
must always be set to a value of 4. The instance value selects the data set to
interface with for the instruction. The Attribute field is not used by the module and
should be set to 0.
For more information on the CIP message support, refer to the sample ladder
logic.
The following topics describe how CIP messages are handled.
CIP Generic Messages
Get Attribute Single (0x0E)
Set Attribute Single (0x10)