EasyManuals Logo

Raven ISOBUS Product Control User Manual

Default Icon
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
CHAPTER
6
Manual No. 016-0171-362 Rev. F 47
CHAPTER 6
TROUBLESHOOTING
Problem Action
1. Rate reads “0. Verify SPEED is registering accurately. If SPEED is zero, refer to
the VT display troubleshooting procedure.
Verify TOTAL VOLUME is registering flow. If not, refer to
problem 6.
2. Rate inaccurate or unstable. Verify that all calibration numbers and settings keyed into the
console are correct. Verify SPEED is registering accurately. If
SPEED is inaccurate, refer to the VT display troubleshooting
procedure.
In MAN (manual) operation, verify that RATE display holds
constant. If not, refer to problem 7.
Confirm that boom section status shown on the display is not
changing.
In MAN (manual) operation, check low end and high end
pressure range. If pressure cannot be adjusted manually, refer to
problem 6.
3. Cannot verify rate in manual operation
or in auto.
Check cabling to motorized control valve for breaks.
Check connections in cabling for cleanliness.
Verify that there is voltage at the valve connector by toggling
master switch ON; AUTO/MAN switch to MAN; and POWER ON.
Manually operate INC/DEC switch to verify voltage.
Verify that valve is turning, if not, replace control valve.
4. Sprayer pressure is correct but RATE is
low.
Verify that nozzle strainer screens or check valves are not
plugged.
Verify that pressure at each boom is the same.
Verify all nozzles are of proper and same orifice size. See
Appendix 8, Calculating the Calibration Values.
5. Total volume does not register. Check flow meter/encoder cable for breaks and shorts. See the
Testing the Flow Meter/Encoder Cable section on page 71.
Check the internal components of the flow meter/encoder;
clean and adjust. Appendix C, Flow Meter Maintenance and
Adjustment Procedure for flow meter cleaning and adjustments.
Replace flow meter transducer/encoder.
6. Total volume registers flow inaccurately. Verify that arrow on flow meter is pointing in direction of flow.
7. Motorized control valve rotates more
than 1/4 turn.
Replace motorized control valve.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raven ISOBUS Product Control and is the answer not in the manual?

Raven ISOBUS Product Control Specifications

General IconGeneral
BrandRaven
ModelISOBUS Product Control
CategoryControl Unit
LanguageEnglish

Related product manuals