Rockwell Automation Publication 1769-UM021I-EN-P - May 2018 95
Complete Software Tasks Required at CompactLogix 5370 Controller Installation Chapter 5
If you click Disable BOOTP/DHCP and it does not disable BOOTP/
DHCP, use RSLinx or the Studio 5000 environment to disable BOOTP/
DHCP.
To disable BOOTP/DHCP from RSLinx, perform the following:
1. Make sure that a USB cable is connected to your computer and the
controller.
2. Start RSLinx Classic software.
After several seconds, an RSWho dialog box appears.
3. If no RSWho dialog box appears, from the Communications pull-down
menu, choose RSWho.
4. Navigate to the USB network.
5. Right-click on the controller and choose Module Configuration.
6. Click the Port Configuration tab.
7. From the Network Configuration Type, click Static to disable
BOOTP/DHCP.
8. Click OK.