Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 113
Logging Chapter 6
Energy_Log_Mode
Energy_Log_Mode defines the log behavior when full:
0 = Stop logging
1 = Delete oldest energy log file and create a new file
Setpoint_Log_Mode
Setpoint_Log_Mode defines the log behavior when full.
0 = Stop logging
1 = Overwrite oldest record
Time_Of_Use_AutoStore
Time_Of_Use_AutoStore defines the day of the month to start a new time-of-
use log record.
Off_Peak_Days
Off_Peak_Days is a bit field that specifies off-peak days of the week.
Bit 0 = Sunday, bit 1 = Monday, and so forth
MID_Peak_AM_Hours
MID_Peak_PM_Hours
ON_Peak_AM_Hours
ON_Peak_PM_Hours
These parameters are bit fields specifying mid-peak and on-peak hours of the
weekdays that are not already defined as off-peak. Bit 0 = 12 a.m. …1 a.m.,
bit 1 = 1 a.m.…2 a.m., and so forth.
Load_Factor_Auto_Log_Setting
Load_Factor_Auto_Log_Setting defines the day of month to start a new load
factor log record.
PowerQuality_Log_Mode
This parameter sets the action of the log once the log has filled to capacity.
0 = Stop logging
1 = Overwrite oldest record