114 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 6 Logging
Event_Log_Mode
Event_Log_Mode defines the log behavior when full.
0 = Stop logging.
1 = Overwrite oldest record.
Retrieve Logging Results from Web Page
You can retrieve logging results from the PowerMonitor 5000 web page. Browse 
to the network address of the power monitor. From the home page, choose the 
LoggingResults folder and then the Data_Log or another logging results page.
To retrieve a file, click the filename link. A dialog box opens asking if you wish to 
open the file (in Microsoft® Excel® or another spreadsheet application), or save the 
file.
Energy and data logs are stored in multiple files. The date and time of the first 
record of each file is embedded in the file name. The date and time of the most 
recent record each file is listed in the file creation date and time columns.