Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 117
Logging Chapter 6
Chronology of Auto Return Data
Selects the chronological order of sequentially retrieved records. This parameter
is ignored if a specific record is requested from the Min/Max, Load Factor, or
TOU log. These values are the choices:
0 = Reverse direction (most recent record first)
1 = Forward direction (oldest record first)
Min/Max Record to be Returned
These values are the choices:
0 = Use sequential return in the order selected
1…207 = Retrieve the selected record. See the Min_Max_Parameter table
for the list
Load Factor or TOU Record to be Returned
These values are the choices:
0 = Use sequential return in the order selected
1 = Retrieve the current active record
2 = Retrieve the latest closed monthly record
13 = Retrieve the earliest closed monthly record
EN 50160 Weekly Record to be Returned
These values are the choices:
0 = Use sequential return in the order selected
1 = Retrieve the current active record
2 = Retrieve the latest closed daily record
8 = Retrieve the earliest closed daily record
EN 50160 Yearly Record to be Returned
These values are the choices:
0 = Use sequential return in the order selected
1 = Retrieve the current active record
2 = Retrieve the latest closed monthly record
13 = Retrieve the earliest closed monthly record