Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 131
Logging Chapter 6
2. Navigate to your controller and click ‘Set Project Path’, then ‘Go Online’.
3. Within the main program, toggle the bit within each rung in this order.
To toggle the bit, you can either right-click on the bit and click toggle or
press Ctrl-T on the keyboard.
RUNG 0 (Config Log Read)
RUNG 1 (Stat Tbl Write)
The use of Rung 1 is optional and can be used to confirm the Wights
(RUNG 0 and RUNG 3) were accepted by the Power Monitor 5000. See
Status.TableWrites
Table 113 on page 346 for additional information.
RUNG 2 (Read File Name)
RUNG 3 (Write File Name)
RUNG 1 (Stat Tbl Write)
Rung 2 must be toggled several times until the Waveform file name of
interest is read. If an empty File Name is read, you have reached the end of
the File Name list. Once read, proceed to Rung 3.
RUNG 4 (Read Waveform)
Rung 4 must toggle on and off several times to read the full file. The
number of times depends on the size of the Waveform file. When all zeros
(00) are returned the file is complete. This read can take some time.
By toggling Rung 4 multiple times, you are selecting which waveform to
retrieve.
IMPORTANT The controller slot is dependent on your controller.