174 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 6 Logging
IEEE1159_Voltage_Fluctuations 12 V1_Pst 1 V1 Pst configured limit has been
exceeded
V2_Pst 2 V2 Pst configured limit has been
exceeded
V3_Pst 3 V3 Pst configured limit has been
exceeded
Voltage_Transient 13 V1_Transient 1 • V1 transient
V2_Transient 2 • V2 transient
V3_Transient 3 • V3 transient
Command_Trigger 14 -- -- • Event triggered by the user command
WSB_Sag 15 -- -- • Sag event from WSB (waveform
synchronization broadcast) message.
WSB_Swell 16 -- -- • Swell event from WSB message
WS B_Transien t 1 7 -- -- • Transient event from WSB message
WSB_Command 18 -- -- • User command from WSB message
IEEE1159_Swell 19 V1_Swell 1 • Voltage Swell greater than 110% of
nominal
V2_Swell 2 • Voltage Swell greater than 110% of
nominal
V3_Swell 3 • Voltage Swell greater than 110% of
nominal
IEEE1159_Sag 20 V1_Sag 1 • Voltage Sag less than 90% of nominal
V2_Sag 2 • Voltage Sag less than 90% of nominal
V3_Sag 3 • Voltage Sag less than 90% of nominal
IEEE1159_Interruption 21 V1_Interruption 1 • Voltage Interruption less than 10%
nominal
V2_Interruption 2 • Voltage Interruption less than 10%
nominal
V3_Interruption 3 • Voltage Interruption less than 10%
nominal
EN61000_4_30_Mains_Signaling 22 V1_Mains_Signal 1 V1 mains signaling has exceeded the
configured limit
V2_Mains_Signal 2 V2 mains signaling has exceeded the
configured limit
V3_Mains_Signal 3 V3 mains signaling has exceeded the
configured limit
EN61000_4_30_Under_Deviation 23 V1_Under_Deviation 1 An under deviation is detected on V1
V2_Under_ Deviation 2 An under deviation is detected on V2
V3_Under_ Deviation 3 An under deviation is detected on V3
EN61000_4_30_Over_Deviation 24 V1_Over_ Deviation 1 An over deviation is detected on V1
V2_Over_ Deviation 2 An over deviation is detected on V2
V3_Over_ Deviation 3 An over deviation is detected on V3
Power Quality Event Name Event Code Sub Event Name Sub Event Code Can Trigger Waveform
Capture
Description