Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 177
Logging Chapter 6
TriggerData_Parameter_4 - 15 = Frequency_Hz
TriggerData_Parameter_5 - 19 = Total_kW
TriggerData_Parameter_6 - 23 = Total_kVAR
TriggerData_Parameter_7 - 27 = Total_kVA
TriggerData_Parameter_8 - 39 = Total_PF_Lead_Lag_Indicator
Operation
When an associated setpoint activates, the trigger data file stores the selected
parameters for the selected duration in a data file and stores the associated
setpoint or logic gate identity and configuration parameters in a setpoint
information file.
File Names
Triggerlog_YYYYMMDD_hhmmss_HH, and
TriggerSetpointInfo_YYYYMMDD_hhmmss_HH, where
YYYMMDD_hhmmss = the local date and time stamp of the record, used
to associate the trigger data file with its associated setpoint information
HH = the UTC hour avoids duplication during daylight-saving time
transition
See Appendix A
, LoggingResults. TriggerData_Header Data Table for the
content and structure of the setpoint information file, and LoggingResults.
TriggerData_Log Data Table for the content and structure of the trigger data file.
Trigger Data Log Results
Trigger data log records can be retrieved from the PowerMonitor 5000 web page
or FTP server. Trigger data log records can also be retrieved sequentially by using
the data table interface.
Figure 31 - Trigger Data Log
When retrieved from the web page or FTP server, the first row in the files is a
header row containing parameter names.