278 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
48 1 SINT RealTimeUpdateRate  Selects the update rate for the realtime table and the setpoint 
calculations. 
0 = Single cycle averaged over 8 cycles
1 = Single cycle averaged over 4 cycles
2 = 1 cycle with no averaging
Meter 
Averaging
0…2
1 SINT Pad08 For alignment purpose
2 INT Pad09 For alignment purpose
52 2 Int16 DeviceFaultAction This parameter determines the action when a unit error occurs.
0 = Halt on error and make status indicator solid red
1 = Reset power monitor hardware 
Error Action 0…1
54 2 Int16 EnergyLogInterval Selects how often a record is logged (minutes).  A value of 0 disables 
periodic logging of records.  A value of -1 causes the logging of records 
to be synchronized to the end of the demand Interval. 
Energy Interval 
(Minutes)
-1…60
56 2 Int16 EnergyLogMode This parameter sets the action of the log once the log has filled to 
capacity.
0 = Fill and Stop
1 = Overwrite oldest record.
Energy Log 
Mode
0…1
58 2 Int16 TOU AutoStoreDay Automatically stores the current record for the month replacing an 
older record if the log is full.  The log holds 12 records plus the current 
record.  
0 = Disable storing records 
1 = Store and clear on the first day of the month
2 = 2nd of month
3 = 3rd day of month
…
31 = 31st day of month
If set to 29…31 the last day of every month stores a record.
AutoStore 0…31
60 1 SINT DemandSource When item ‘Demand Broadcast Master Select’ of the Ethernet table is 
set to a master selection of 0…2 sets the type of master input.  In this 
case item ‘3’ is ignored.  When the ‘Demand Broadcast Master Select’ 
of the Ethernet table is set to slave, then any of these inputs can set 
the end of the demand period.  
0 = Internal Timer
1 = Status Input 2
2 = Controller Command
3 = Ethernet Demand Broadcast
Demand Period 
Length
0…3
1 SINT Pad10 For alignment purpose
2 INT Pad11 For alignment purpose
64 1 SINT DemandPeriodLength Specifies the desired period for demand calculations. When set to 0 
there is no projected demand calculations. If the internal timer is 
selected a setting of 0 turns the demand function off.
Number 
Demand 
Periods
0…99
1 SINT Pad12 For alignment purpose
2 INT Pad13 For alignment purpose
68 1 SINT NumberOfDemandCycles Specifies the number of demand periods to average for demand 
measurement.
Demand Sync 
Delay
1…15
1 SINT Pad14 For alignment purpose
2 INT Pad15 For alignment purpose
Table 45 - Configuration.Instance Data Table (continued)
Start 
Byte
Size Type Tag Name Description Units Range