Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 279
PowerMonitor 5000 Unit Data Tables Appendix A
72 2 Int16 ForcedDemandSyncDelay When the power monitor is configured for external demand control 
the unit delays for xxx seconds after the expected control pulse has 
not been received. The demand period starts over and a record is 
recorded in the event log  
0 = Wait forever
1…900 = Wait this many seconds before starting a new demand 
period. 
IMPORTANT: This setting becomes active when an external input is 
used to end the demand period.
Demand 
Broadcast 
Mode
0…900
2 INT Pad16 For alignment purpose
76 1 SINT DemandBroadcastMode Demand Ethernet broadcast selection.  
0 = Slave
1 = Master
IMPORTANT:  There can be only one master per demand network.
Demand 
Broadcast 
Mode
0…1
1 SINT Pad17 For alignment purpose
78 2 Int16 DemandBroadcastPort The common port for demand broadcast messages. Demand 
Broadcast Port
300…400
80 1 SINT KYZOutputMode The parameter selected pulses the KYZ output at a rate that equals the 
parameter value divided by KYZ scale.  
0 = Setpoint Control  
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
KYZ Output 
Parameter
0…6
1 SINT Pad18 For alignment purpose
2 INT Pad19 For alignment purpose
84 4 Int32 KYZPulseScale The KYZ output parameter divided by the scale is the output pulse 
rate.  Example:  Wh is selected for the parameter and 1,000 is the 
scale value.  The output is pulsed every kWh.
KYZ Output 
Scale
1…100,000
88 2 Int16 KYZPulseDuration Set as 50…1000 to indicate the duration of the pulse in milliseconds, 
or set to 0 for KYZ-style transition output. (Toggle)  
IMPORTANT: The value for delay is rounded off to the nearest 10 ms 
internally during this function.
KYZ Output 
Duration
0 or 50…1000
2 INT Pad20 For alignment purpose
92 1 SINT R1OutputMode The parameter selected pulses the relay 1 output at a rate that equals 
the parameter value divided by relay 1 scale.  
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
Relay 1 Output 
Parameter
0…6
1 SINT Pad21 For alignment purpose
2 INT Pad22 For alignment purpose
96 4 Int32 R1PulseScale The relay 1 output parameter divided by the relay 1 scale is the output 
pulse rate. Example: Wh is selected for the parameter and 1,000 is the 
scale value. The output is pulsed every kWh.
Relay 1 Output 
Scale
1…100,000
Table 45 - Configuration.Instance Data Table (continued)
Start 
Byte
Size Type Tag Name Description Units Range