280 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
100 2 Int16 R1PulseDuration Set as 50…1000 to indicate the duration of the pulse in milliseconds,
or set to 0 for KYZ-style transition output. (Toggle)
IMPORTANT: The value for delay is rounded off to the nearest 10 ms
internally during this function.
Relay 1 Output
Duration
0 or 50…1000
2 INT Pad23 For alignment purpose
104 1 SINT R2OutputMode The parameter selected pulses the relay 2 output at a rate that equals
the parameter value divided by relay 2 scale.
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
Relay 2 Output
Parameter
0…6
1 SINT Pad24 For alignment purpose
2 INT Pad25 For alignment purpose
108 4 Int32 R2PulseScale The relay 2 output parameter divided by the relay 2 scale is the output
pulse rate. Example: Wh is selected for the parameter and 1,000 is the
scale value. The output is pulsed every kWh.
Relay 2 Output
Scale
1…100,000
112 2 Int16 R2PulseDuration Set as 50…1000 to indicate the duration of the pulse in milliseconds,
or set to 0 for KYZ-style transition output. (Toggle)
IMPORTANT: The value for delay is rounded off to the nearest 10 ms
internally during this function.
Relay 2 Output
Duration
0 or 50…1000
2 INT Pad26 For alignment purpose
116 1 SINT R3OutputMode The parameter selected pulses the relay 3 output at a rate that equals
the parameter value divided by relay 3 scale.
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
Relay 3 Output
Parameter
0…6
1 SINT Pad27 For alignment purpose
2 INT Pad28 For alignment purpose
120 4 Int32 R3PulseScale The relay 3 output parameter divided by the relay 3 scale is the output
pulse rate. Example: Wh is selected for the parameter and 1,000 is the
scale value. The output is pulsed every kWh.
Relay 3 Output
Scale
1…100,000
124 2 Int16 R3PulseDuration Set as 50…1000 to indicate the duration of the pulse in milliseconds,
or set to 0 for KYZ-style transition output. (Toggle)
IMPORTANT: The value for delay is rounded off to the nearest 10 ms
internally during this function.
Relay 3 Output
Duration
0 or 50…1000
2 INT Pad29 For alignment purpose
128 4 Int32 S1ScaleFactor When a status pulse is received the count is increased by the scale
factor. (Input pulse * input scale) added to total status count.
Status 1 Input
Scaling
1…1,000,000
132 4 Int32 S2ScaleFactor When a status pulse is received the count is increased by the scale
factor. (Input pulse * input scale) added to total status count.
Status 2 Input
Scaling
1…1,000,000
136 4 Int32 S3ScaleFactor When a status pulse is received the count is increased by the scale
factor. (Input pulse * input scale) added to total status count.
Status 3 Input
Scaling
1…1,000,000
140 4 Int32 S4ScaleFactor When a status pulse is received the count is increased by the scale
factor. (Input pulse * input scale) added to total status count.
Status 4 Input
Scaling
1…1,000,000
Table 45 - Configuration.Instance Data Table (continued)
Start
Byte
Size Type Tag Name Description Units Range