282 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
156 1 SINT R3CommFaultMode The Default output state on communication loss defines the behavior 
of the output if the power monitor experiences a loss of 
communication. 
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local Control
N/A 0…4
1 SINT Pad36 For alignment purpose
2 Int16 CmdWordOne These commands can be sent to the power monitor.  When using the 
optional elements the command table must be sent complete with all 
elements present. If the single password table is used to gain access to 
configuration items then the command can be sent alone without 
optional settings.  The command options are: 
0 = No Action 
1 = Set kWh Register  
2 = Set kVARh Register  
3 = Set kVAh Register  
4 = Set kAh Register 
5 = Clear All Energy Registers  
6 = Set Status 1 Count  
7 = Set Status 2 Count  
8 = Set Status 3 Count  
9 = Set Status 4 Count  
10 = Force KYZ Output On  
11 = Force KYZ Output Off  
12 = Remove Force from KYZ  
13 = Force Relay 1 Output On  
14 = Force Relay 1 Output Off  
15 = Remove Force from Relay 1  
16 = Force Relay 2 Output On  
17 = Force Relay 2 Output Off  
18 = Remove Force from Relay 2  
19 = Force Relay 3 Output On  
20 = Force Relay 3 Output Off  
21 = Remove Force from Relay 3 
22 = Restore Factory Defaults 
23 = Reset Powermonitor System 
24 = Reserved for future use.  
IMPORTANT:  If a command is received that is not supported by your 
catalog number, the command is ignored.
N/A 0…23
Table 45 - Configuration.Instance Data Table (continued)
Start 
Byte
Size Type Tag Name Description Units Range