Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 283
PowerMonitor 5000 Unit Data Tables Appendix A
Configuration Parameter Object Table
Table 46 - Table Properties
CIP Class Code 0x0F
No. of Parameters  52
Data Type Varies
Data Access Read/Write
TIP See Table 45 Configuration.Instance Data Table for descriptions of each 
parameter.
Table 47 - Configuration Parameter Object Table
Instance Number Parameter Object Name Type Units Range Default Value
1 Metering_Mode SINT N/A 0…10 2
2 V1_V2_V3_PT_Primary Real V 0…1,000,000 480
3 V1_V2_V3_PT_Secondary Real V 0…690 480
4 I1_I2_I3_CT_Primary Real A 0…1,000,000 5
5 I1_I2_I3_CT_Secondary SINT A 5 5
6 VN_PT_Primary Real V 0…1,000,000 480
7 VN_PT_Secondary Real V 0…690 480
8 I4_CT_Primary Real A 0…1,000,000 5
9 I4_CT_Secondary SINT A 5 5
10 Nominal_System_LL_Voltage Real V 0…1,000,000 480
11 Reserved Real N/A 0 0
12 Nominal_System_Frequency Real Hz 50 or 60 60
13 Realtime_Update_Rate SINT N/A 0…2 0
14 Date_Year Int16 Year 2010…2100 2010
15 Date_Month Int16 Mon 1…12 1
16 Date_Day Int16 Day 1…31 1
17 Time_Hour Int16 Hour 0…23 0
18 Time_Minute Int16 Min 0…59 0
19 Time_Seconds Int16 Sec 0…59 0
20 Time_Milliseconds Int16 Mise 0…999 0
21 Unit_Error_Action Int16 N/A 0…1 1
22 Energy_Log_Interval Int16 N/A -1…60 15
23 Energy_Log_Mode Int16 N/A 0…1 1
24 Time_Of_Use_AutoStore Int16 N/A 0…31 31
25 Demand_Source SINT N/A 0…3 0
26 Demand_Period_Length SINT N/A 0…99 15
27 Number_Demand_Periods SINT N/A 1…15 1
28 Forced_Demand_Sync_Delay Int16 N/A 0…900 10