326 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
Configuration.Log_Read
Table 76 - Table Properties
CIP Instance Number 814
PCCC File Number N23
No. of Elements 15
Length in Words 15
Data Type Int16
Data Access Read/Write
Table 77 - Configuration.Log_Read Data Table
Element
Number
Type Tag Name Description Default Range
0 Int16 Selected Log Selects the log that information is returned from. Once a single request has
been made the auto return feature brings back successive records each time the
log is read. Some logs support individual record requests.
1 = Unit Event Log
2 = Min/Max Log
3 = Load Factor Log
4 = Time of Use Log
5 = Setpoint Log
6 = Alarm Log
7 = Data Log File List
8 = Energy Log File List
9 = Snapshot Log File
10 = Power Quality Log
11 = Waveform Log File
12 = Trigger Data File
13 = Trigger Header File
14 = EN50160 Weekly Log
15 = EN50160 Yearly Log
Important: If your catalog number does not support the requested log item,
the power monitor ignores the request. Check the Write Status Table.
Initial value = 0 1…15
1Int16Chronology of
Auto Return Data
The date chronology of the returned records.
0 = Reverse direction
1 = Forward direction.
101
2 Int16 The Min/Max
record to be
returned
Selects the Min/Max record number to be returned. See the table for Min/Max
record list.
0 0….82 (M5,M6)
0….207 (M8)
3 Int16 Load Factor or
TOU record to be
returned.
Selects the Load Factor or TOU record number to be returned.
0 = Use incremental return and the chronology selected.
1…13 selects an individual record.
1 = Current record being calculated.
0 0…13
4 Int16 EN50160 weekly
record to be
returned
Selects the EN50160 weekly record number to be returned.
0 = Use incremental return and the chronology selected.
1…8 selects an individual record.
1 = Current record being calculated.
008
5 Int16 EN50160 yearly
record to be
returned
Selects the EN50160 yearly record number to be returned.
0 = Use incremental return and the chronology selected.
1…13 selects an individual record.
1 = Current record being calculated.
0 0…13
6…14 Int16 Reserved Reserved for future use. 0 0