EasyManua.ls Logo

Rockwell Automation Allen-Bradley PowerMonitor 5000 Unit - Page 349

Rockwell Automation Allen-Bradley PowerMonitor 5000 Unit
514 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 349
PowerMonitor 5000 Unit Data Tables Appendix A
2 Int16 Logic_Level_1_Gates_Active (M6 and M8) Actuation Status of Level 1 Gates 0 … 65535
Bit 0 Level1_Gate1_Output 1 Indicates gate logic output is true 0 or 1
Bit 1 Level1_Gate2_Output 1 Indicates gate logic output is true 0 or 1
Bit 2 Level1_Gate3_Output 1 Indicates gate logic output is true 0 or 1
Bit 3 Level1_Gate4_Output 1 Indicates gate logic output is true 0 or 1
Bit 4 Level1_Gate5_Output 1 Indicates gate logic output is true 0 or 1
Bit 5 Level1_Gate6_Output 1 Indicates gate logic output is true 0 or 1
Bit 6 Level1_Gate7_Output 1 Indicates gate logic output is true 0 or 1
Bit 7 Level1_Gate8_Output 1 Indicates gate logic output is true 0 or 1
Bit 8 Level1_Gate9_Output 1 Indicates gate logic output is true 0 or 1
Bit 9 Level1_Gate10_Output 1 Indicates gate logic output is true 0 or 1
Bit 10 … 15 Reserved Future Use 0
3 Int16 Metering_Status Metering Conditions Status 0…65,535
Bit 0 Virtual_Wiring_Correction 1 = Virtual Wiring Correction ON 0…1
Bit 1 Volts_Loss_V1 1 = Loss of V1 metering voltage 0…1
Bit 2 Volts_Loss_V2 1 = Loss of V2 metering voltage 0…1
Bit 3 Volts_Loss_V3 1 = Loss of V3 metering voltage 0…1
Bit 4 Volts_Over_Range_Indication 1 = A Voltage over range status condition exists 0…1
Bit 5 Amps_Over_Range_Indication 1 = An Amperage over range status condition exists 0…1
Bit 6 Wiring_Diagnostics_Active 1 = The wiring diagnostics is currently calculating wiring
condition
0…1
Bit 7…15 Reserved Reserved for future use 0
4 Int16 Over_Range_Information Indicates which input is over range 0…65,535
Bit 0 V1G_Over_Range 1 = V1G input is over input range 0…1
Bit 1 V2G_Over_Range 1 = V2G input is over input range 0…1
Bit 2 V3G_Over_Range 1 = V3G input is over input range 0…1
Bit 3 VNG_Over_Range 1 = VNG input is over input range 0…1
Bit 4 I1_Over_Range 1 = I1 input is over input range 0…1
Bit 5 I2_Over_Range 1 = I2 input is over input range 0…1
Bit 6 I3_Over_Range 1 = I3 input is over input range 0…1
Bit 7 I4_Over_Range 1 = I4 input is over input range 0…1
Bit 8…15 Reserved Reserved for future use 0
Table 117 - Status.Alarms Data Table (continued)
Element
Number
Type Tag Name Description Range

Table of Contents

Related product manuals