350 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
5 Int16 PowerQuality_Status Power Quality Conditions Status 0…65,535
Bit 0 Sag_Indication_Detected 1 = A sag event was detected in the last metering cycle 0…1
Bit 1 Swell_Indication_Detected 1 = A Swell event was detected in the last metering cycle 0…1
Bit 2 Transient_Indication A transient occurred 0…1
Bit 3 200mS_Sag_Swell_Status_Flag A flag indicating 200 ms result has been calculated during a
Sag, Swell, or Interruption
0…1
Bit 4 3s_Sag_Swell_Status_Flag A flag indicating the 3 s result has been calculated during a Sag,
Swell, or Interruption
0…1
Bit 5 10m_Sag_Swell_Status_Flag A flag indicating the 10 min result has been calculated during a
Sag, Swell, or Interruption
0…1
Bit 6 2h_Sag_Swell_Status_Flag A flag indicating the 2h result has been calculated during a Sag,
Swell, or Interruption
0…1
Bit 7…15 Reserved Reserved for future use 0
6 Int16 Logs_Status Logs Condition Status 0… 65,535
Bit 0 Data_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80%
filled
0…1
Bit 1 Event_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80%
filled
0…1
Bit 2 Setpoint_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80%
filled
0…1
Bit 3 PowerQuality_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80%
filled
0…1
Bit 4 Energy_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80%
filled
0…1
Bit 5 Waveform_Full Is Set when log is at least 80% filled 0…1
Bit 6 TriggerData_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80%
filled
0…1
Bit 7…15 Reserved Reserved for future use 0
7 Int16 Output_Pulse_Overrun The output pulse rate exceeds the configured capability 0…65535
Bit 0 KYZ_Pulse_Overrun The KYZ output pulse rate exceeds the configured capability 0…1
Bit 1 Relay1_Pulse_Overrun The Relay 1 output pulse rate exceeds the configured capability
Bit 2 Relay2_Pulse_Overrun The Relay 2 output pulse rate exceeds the configured capability
Bit 3 Relay3_Pulse_Overrun The Relay 3 output pulse rate exceeds the configured capability
Bit 4…15 Reserved Reserved for future use 0
8 Int16 IEEE1159_Over_Voltage Over Voltage Condition 0…65535
Bit 0 IEEE1159_Over_Voltage_V1 1 = An over voltage is detected on V1 0…1
Bit 1 IEEE1159_Over_Voltage_V2 1 = An over voltage is detected on V2 0…1
Bit 2 IEEE1159_Over_Voltage_V3 1 = An over voltage is detected on V3 0…1
Bit 3…15 Reserved Reserved for future use 0
Table 117 - Status.Alarms Data Table (continued)
Element
Number
Type Tag Name Description Range