PowerMonitor 5000 Unit Data Tables Appendix A
9 Int16 IEEE1159_Under_Voltage Under Voltage Condition 0…65535
Bit 0 IEEE1159_Under_Voltage_V1 1 = An under voltage is detected on V1 0…1
Bit 1 IEEE1159_Under_Voltage_V2 1 = An under voltage is detected on V2 0…1
Bit 2 IEEE1159_Under_Voltage_V3 1 = An under voltage is detected on V3 0…1
Bit 3…15 Reserved Reserved for future use 0
10 Int16 IEEE1159_Imbalance_Condition IEEE1159 Imbalance 0…65535
Bit 0 IEEE1159_Imbalance_Condition_Volts 1 = An Imbalance is detected on Voltage 0…1
Bit 1 IEEE1159_Imbalance_Condition_Current 1 = An Imbalance is detected on Current 0…1
Bit 2…15 Reserved Reserved for future use 0
11 Int16 IEEE1159_DCOffset_Condition IEEE1159 DC Offset Condition 0…65535
Bit 0 IEEE1159_DCOffset_Condition_V1 1 = A DC offset exceed limitation is detected on V1 0…1
Bit 1 IEEE1159_DCOffset_Condition_V2 1 = A DC offset exceed limitation is detected on V2 0…1
Bit 2 IEEE1159_DCOffset_Condition_V3 1 = A DC offset exceed limitation is detected on V3 0…1
Bit 3…15 Reserved Reserved for future use 0
12 Int16 IEEE1159_Voltage_THD_Condition IEEE1159 Voltage THD Condition 0…65535
Bit 0 IEEE1159_Voltage_THD_Condition_V1 1 = A THD exceed limitation is detected on V1 0…1
Bit 1 IEEE1159_Voltage_THD_Condition_V2 1 = A THD exceed limitation is detected on V2 0…1
Bit 2 IEEE1159_Voltage_THD_Condition_V3 1 = A THD exceed limitation is detected on V3 0…1
Bit 3 IEEE1159_Voltage_TID_Condition_V1 1 = A TID exceed limitation is detected on V1 0…1
Bit 4 IEEE1159_Voltage_TID_Condition_V2 1 = A TID exceed limitation is detected on V2 0…1
Bit 5 IEEE1159_Voltage_TID_Condition_V3 1 = A TID exceed limitation is detected on V3 0…1
Bit 6…15 Reserved Reserved for future use 0
13 Int16 IEEE1159_Current_THD_Condition IEEE1159 Current THD Condition 0…65535
Bit 0 IEEE1159_Current_THD_Condition_ I1 1 = A THD exceed limitation is detected on I1 0…1
Bit 1 IEEE1159_Current_THD_Condition_ I2 1 = A THD exceed limitation is detected on I2 0…1
Bit 2 IEEE1159_Current_THD_Condition_ I3 1 = A THD exceed limitation is detected on I3 0…1
Bit 3 IEEE1159_Current_THD_Condition_I4 1 = A THD exceed limitation is detected on I4 0…1
Bit 4 IEEE1159_Current_TID_Condition_I1 1 = A TID exceed limitation is detected on I1 0…1
Bit 5 IEEE1159_Current_TID_Condition_I2 1 = A TID exceed limitation is detected on I2 0…1
Bit 6 IEEE1159_Current_TID_Condition_I3 1 = A TID exceed limitation is detected on I3 0…1
Bit 7 IEEE1159_Current_TID_Condition_I4 1 = A TID exceed limitation is detected on I4 0…1
Bit 8…15 Reserved Reserved for future use 0
14 Int16 IEEE1159_PowerFrequency_Condition IEEE1159 Power Frequency Condition 0…65535
Bit 0 IEEE1159_PowerFrequency_Condition 1 = Frequency exceed limitation is detected 0…1
Bit 1…15 Reserved Reserved for future use 0
Table 117 - Status.Alarms Data Table (continued)