Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 405
PowerMonitor 5000 Unit Data Tables Appendix A
28 Real 200mS_V2_N_IEC_THD_% V2-N IEC Total Harmonic Distortion % 0.00…100.00
29 Real 200mS_V3_N_IEC_THD_% V3-N IEC Total Harmonic Distortion % 0.00…100.00
30 Real 200mS_VN_G_IEC_THD_% VN-G IEC Total Harmonic Distortion % 0.00…100.00
31 Real 200mS_Avg_IEC_THD_V_% Average V1/V2/V3 to N IEC Total Harmonic Distortion % 0.00…100.00
32 Real 200mS_V1_V2_IEC_THD_% V1-V2 IEC Total Harmonic Distortion % 0.00…100.00
33 Real 200mS_V2_V3_IEC_THD_% V2-V3 IEC Total Harmonic Distortion % 0.00…100.00
34 Real 200mS_V3_V1_IEC_THD_% V3-V1 IEC Total Harmonic Distortion % 0.00…100.00
35 Real 200mS_Avg_IEC_THD_V_V_% Average IEC THD  for V1-V2, V2-V3, V3-V1 % 0.00…100.00
36 Real 200mS_I1_IEC_THD_% I1 IEC Total Harmonic Distortion % 0.00…100.00
37 Real 200mS_I2_IEC_THD_% I2 IEC Total Harmonic Distortion % 0.00…100.00
38 Real 200mS_I3_IEC_THD_% I3 IEC Total Harmonic Distortion % 0.00…100.00
39 Real 200mS_I4_IEC_THD_% I4 IEC Total Harmonic Distortion % 0.00…100.00
40 Real 200mS_Avg_IEC_THD_I_% Average I1/I2/I3 IEC Total Harmonic Distortion % 0.00…100.00
41 Real 200mS_I1_K_Factor I1 K-factor - 1.00…25,000.00
42 Real 200mS_I2_K_Factor I2 K-factor - 1.00…25,000
43 Real 200mS_I3_K_Factor I3 K-factor - 1.00…25,000.00
44 Real 200mS_Sag_Swell_Status_Flag A flag indicating 200 ms result has been calculated during a Sag, Swell, or 
Interruption.
#0…1
45 Real 200mS_Metering_Iteration A number 0…9,999,999 that indicates that the metering functions and 
internal communications are updating.
# 0…9,999,999
Table 189 - PowerQuality.EN61000_4_30_THD (continued)
Element 
Number
Type Tag Name Description Units Range