406 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix A PowerMonitor 5000 Unit Data Tables
PowerQuality.EN61000_4_30_Sequence (M8 only)
Table 190 - Table Properties
CIP Instance Number 882
PCCC File Number F91
No. of Elements 13
Length in Words 26
Data Type Real
Data Access Read only
Applies to M8 only
Table 191 - PowerQuality.EN61000_4_30_Sequence Data Table
Element
Number
Type Tag Name Description Units Range
0 Real 200mS_Metering_Date_Stamp Date of cycle collection MM:DD:YY MMDDYY 0…123,199
1 Real 200mS_Metering_Time_Stamp Time of cycle collection HH:MM:SS hhmmss 0…235,959
2 Real 200mS_Metering_uSecond_Stamp Microsecond of cycle collection uS 0.000…999,999
3 Real 200mS_Pos_Seq_Volts Positive Sequence Voltage V 0…9.999E15
4 Real 200mS_Neg_Seq_Volts Negative Sequence Voltage V 0…9.999E15
5 Real 200mS_Zero_Seq_Volts Zero Sequence Voltage V 0…9.999E15
6 Real 200mS_Pos_Seq_Amps Positive Sequence Amps A 0…9.999E15
7 Real 200mS_Neg_Seq_Amps Negative Sequence Amps A 0…9.999E15
8 Real 200mS_Zero_Seq_Amps Zero Sequence Amps A 0…9.999E15
9 Real 200mS_Voltage_Unbalance_% Voltage percent unbalance % 0.00…100.00
10 Real 200mS_Current_Unbalance_% Current percent unbalance % 0.00…100.00
11 Real 200mS_Sag_Swell_Status_Flag A flag indicating 200 ms result has been calculated during a Sag, Swell, or
Interruption.
%01
12 Real 200mS_Metering_Iteration A number 0…9,999,999 that indicates that the metering functions and
internal communications are updating.
% 0…9,999,999