EasyManua.ls Logo

Rockwell Automation Allen-Bradley PowerMonitor 5000 Unit - Page 488

Rockwell Automation Allen-Bradley PowerMonitor 5000 Unit
514 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
488 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Appendix I EN 61000-4-30 Metering and Aggregation
Supply Voltage Unbalance
Supply voltage unbalance is evaluated by using the method of symmetrical
components, at the basic 10/12 cycle metering rate, and by using filtering to
minimize the effects of harmonics. Measurement uncertainty must be less than
±0.15% of both negative sequence ratio and zero-sequence ratio.
The 10/12 cycle results of positive, negative, and zero-sequence component
values on all voltage and current channels, and the 10/12 cycle results of voltage
and current percent unbalance, are returned in the
PowerQuality.EN61000_4_30_Sequence Data Table
. Three-second, 10 minute,
and 2-hour time aggregations of voltage unbalance are returned in the
PowerQuality.EN61000_4_30_Aggregation Data Table
.
Voltage Harmonics and Interharmonics
Harmonic and Interharmonic groups are measured by using the requirements of
IEC 61000-4-7, at the basic 10/12 cycle metering rate. Measurement accuracy is
specified as follows:
For voltage and current harmonics, the measurement uncertainty is no
greater than ±1% of the measured fundamental voltage or current.
The phase shift between individual channels must be less than h * 1°.
The PowerMonitor 5000 M8 model provides the following sets of harmonic
measurements in accordance with EN 61000-4-30.
10/12 cycle voltage and current IEEE and IEC THD, crest factor, and K-
factor, in the following data table:
PowerQuality.EN61000_4_30_THD (M8 only)
10/12 cycle THD voltage THD of harmonic (THDS) and interhamonic
(TIHDS) subgroups, in the following data table:
PowerQuality.EN61000_4_30_HSG (M8 only)
Harmonic subgroup up to the 50th harmonic for voltage and current
updated every 10/12 cycles (200 mS). These results are reported in the
following data tables:
PowerQuality.200mS_V1_N_Volts_RMS_HDS
PowerQuality.200mS_V2_N_Volts_RMS_HDS
PowerQuality.200mS_V3_N_Volts_RMS_HDS
PowerQuality.200mS_VN_G_Volts_RMS_HDS
PowerQuality.200mS_V1_V2_Volts_RMS_HDS
PowerQuality.200mS_V2_V3_Volts_RMS_HDS
TIP You can also set up user-configurable voltage interruption detection in the
PowerMonitor 5000 M6 and M8 models. See
Sag and Swell Detection on
page 102.

Table of Contents

Related product manuals