Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 55
Setup and Commands Chapter 3
Optional DeviceNet Communication Setup
Choose the Configuration folder and choose the OptionalComm page, which 
lets you set the address and communication rate to operate in your system. The 
range for DeviceNet_Address is 0…63 (default). The selections for 
DeviceNet_Baudrate are the following:
• 0 = 125 Kbps (default)
• 1 = 250 Kbps
• 2 = 500 Kbps
•3 = Autobaud
Refer to
Optional DeviceNet Communication on page 221 for more 
information on optional DeviceNet® communication parameters.
Optional ControlNet Communication Setup
Choose the Configuration folder and then choose the OptionalComm page. The 
ControlNet® address is the only configurable parameter. The default is 255.
Configure Date and Time
Follow these steps to set the date and time.
1. Choose the Configuration folder and choose the DateTime page. 
2. Enter the year, month, day, hour, and minute into the corresponding input 
fields and click Apply Changes. 
If your power monitor is configured for time synchronization with either 
an SNTP or IEEE 1588 PTP server, the time is already set.
IMPORTANT You can also configure or change the DeviceNet port parameters by using 
RSNetWorx™ for DeviceNet software or similar utilities.