Rockwell Automation Publication 1426-UM001J-EN-P - August 2019 75
Metering Chapter 4
Wiring diagnostic results can also be used for automatic virtual wiring correction,
as described in the next section.
Applications
Wiring diagnostics applies to all models.
Setup
Only basic metering setup is required.
Command
Command Word 2
Set this command word value to 11 (decimal) or make selection in web page to
initiate wiring diagnostics.
Wiring Diagnostic Results
The PowerMonitor 5000 unit returns the following wiring diagnostic results for
all three power factor ranges. Results are available for about 30 minutes after the
command is received.
Command_Status Values
0 = Command Active
1 = Input Level Low
2 = Disabled
3 = Waiting Command