76 Rockwell Automation Publication 1426-UM001J-EN-P - August 2019
Chapter 4 Metering
RangeN_Voltage_Input_Missing
RangeN_Current_Input_Missing
These values are for these parameters:
-1 = Test not run
0 = Test passed
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing
Range1_L97_C89_Status
Range2_L85_C98_Status
Range3_L52_L95_Status
0 = pass
1 = fail
RangeN_Voltage_Input_Inverted
RangeN_Current_Input_Inverted
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
Voltage_Rotation
Current_Rotation
123…321 designating phase and rotation.
Example: 213 = Phase 2 then phase 1 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
Phasor Magnitudes and Angles
The PowerMonitor 5000 unit updates these values continually.