Reference Manual
00809-0100-4664, Rev BA
January 2010
Rosemount 8712
E-8
ABB Magmaster MFE
and MFF Sensors (New
Version) to Rosemount
8712 Transmitter
Connect coil drive and electrode cables as shown in Figure E-6.
Figure E-6. Wiring Diagram for
ABB Magmaster MFE and MFF
Sensors (New Version) and
Rosemount 8712
Table E-4. ABB Magmaster MFE and MFF Sensors (New Version) Wiring
Connections
Rosemount 8712
ABB Magmaster MFE and
MFF Sensors (New Version)
1Red
2 Yellow
17
18 Pink
19 Blue
Grey
Pink
Blue
White
Violet
Yellow
Red
ABB MAGMASTER MFE
AND MFF SENSORS
(NEW VERSION)
ROSEMOUNT 8712
TRANSMITTER
This is a pulsed dc magnetic flowmeter. Do
not connect ac power to the sensor or
to terminals 1 and 2 of the transmitter,
or replacement of the electronics board will
be necessary.