Reference Manual
00809-0100-4664, Rev BA
January 2010
E-31
Rosemount 8712
Krohne Optiflux Sensor
to Rosemount 8712
Transmitter
Connect coil drive and electrode cables as shown in Figure E-29.
Figure E-29. Wiring Diagram for
Krohne Optiflux Sensors and
Rosemount 8712
Table E-27. Krohne Optiflux Sensor Wiring Connections
Rosemount 8712 Krohne Optiflux Sensor Sensors
18
2 7
Coil Shield
17 Electrode Shield
18 2
19 3
3
2
1
8
7
4
ROSEMOUNT 8712
TRANSMITTER
KROHNE
SENSORS
This is a pulsed DC magnetic flowmeter.
Do not connect AC power to the sensor
or to terminals 1 and 2 of the
transmitter, or replacement of the
electronics board will be necessary.