6-3
Model 8732C Specifications and Reference Data
Standard Hazardous Locations Certifications
Factory Mutual (FM) Approval
Approved for Class I, Division 2, Groups A, B, C, and D; Class II,
Division 1, Groups E, F, and G; Class III hazardous locations.
Canadian Standards Association (CSA) Approval
Approved for Class I Division 2, Groups A, B, C, and D; Class II,
Division 1, Groups E, F, and G; Class III hazardous locations.
Optional Hazardous Locations Certifications
FM Approval (E5)
Approved for Explosion-Proof Class I, Division 1, Groups C and D.
KEMA/CENELEC Approval (ED)
EEx d IIB T6.
Special Conditions
If the Magnetic Flowmeter Transmitter Type 8732C is used integrally
with certified Magnetic Flowmeter Types 8705 or 8711, it shall
be assured that the mechanical contact areas of the 8705 or 8711
and the 8732C comply with the requirements for flanged joints,
EN 50018-1877, clause 4.1.
Performance
Specifications
(System specifications are given using the frequency output and with the unit at
reference conditions.)
Accuracy
With Model 8705 Flowtube:
System accuracy is ±0.5% of rate from 1 to 30 ft/s (0.3 to 10 m/s);
below 1.0 ft/s (0.3 m/s), the system has an accuracy of ±0.005 ft/s
(0.0015 m/s). Analog output has the same accuracy as frequency
output plus an additional 0.05% of span.
With Model 8711 Flowtube:
System accuracy is ±0.5% of rate from 3 to 30 ft/s (0.9 to 10 m/s);
below 3 ft/s (0.9 m/s), the system has an accuracy of ±0.015 ft/s
(0.045 m/s). Analog output has the same accuracy as frequency output
plus an additional 0.05% of span.
Repeatability
±0.1% of reading.
Response Time
0.2 seconds maximum response to step change in input.
Stability
±0.1% of rate over six months.
Ambient Temperature Effect
±0.25% change over operating temperature range.
EMC Compliance
Complies with the increased requirements from the NAMUR
Recommendations: May 1993, Part 1. Electromagnetic compatibility
(EMC) for process and laboratory apparatus.
Vibration Effect
Meets IEC 770 Pipeline Installation Conditions.