SYSTEM PARAMETERS—SERVICE LEVEL 2 PARAMETERS
32
P. 0 2 5 0–20 seconds Pre-warning time before close
NOTE: This parameter is used for the yellow flashing
warning lights. Increasing the value will increase
the number of times the yellow LED's flash previ-
ous to closing.
3
P. 0 2 6 0–1 Pre-warning time before opening 0
P.050
(Defrost
System Only)
0–3 Heater status
0: Off
1: On — low heat stage 1 heated blower or heat lamps
2: On — medium heat stage 1 + 2 heated blower
3: On — high heat stage 1 + 2 + 3 heated blower
0
P.051
(Defrost
System Only)
0–1 Heater control (parameter P.050 must be on)
0: Manual
1: Automatic timer. Timer settings found in parameters P:058
(time heater is ON), and P:059 (time heater is OFF)
0
P.055
(Defrost
System Only)
0–3 Blower control
0: Off
1: Low speed
2: High speed
3: Automatic (blower runs at high speed when door is open)
0
P.058
(Defrost
System Only)
5–600 minutes Heater timer on time 30
P.059
(Defrost
System Only)
5–600 minutes Heater timer off time 5
P. 2 1 0 0–5 Limit set-up
0: Off
1: Open, close, and partial set-up (partial set using P.244)
2: Open
3: Open and close
4: Partial (P.244 ignored)
5: All (partial set using P.244)
0
P. 2 2 1 ± 125 increments Close-limit adjustment
(For minor adjustments to the close position of the door. This
adjustment resets to 0 if the limits are reset. 10 increments
equals approximately 1 inch of door travel.)
0
P. 2 3 1 ± 60 increments Open-limit adjustment
(For minor adjustments to the open position of the door. This
adjustment resets to 0 if the limits are reset. 10 increments
equals approximately 1 inch of door travel.)
0
P. 2 4 4 0–3 Partial position
0: Parameter off
1: Half-open position
2: Two-thirds-open position
3: Operator-established position
0