9-14
Multi-Accel/Decel time setting via Multi-function terminals
Group Code Parameter Name Set Range Initial Unit
Drive
group
ACC
[Accel time]
-
0 ~
6000
5.0 Sec
dEC
[Decel time]
-
0 ~
6000
10.0 Sec
I/O
group
I17 [Multi-function input terminal P1 define] 0
0 ~ 29
0
I18 [Multi-function input terminal P12 define] 1 1
I19
[Multi-function input terminal P3
define]
8
2
I20
[Multi-function input terminal P4
define]
9
3
I21
[Multi-function input terminal P5
define]
10
4
I34 [Multi-Accel time 1] -
0 ~
6000
3.0
Sec
~ ~
I47 [Multi-Decel time 7] - 9.0
Set I19, I20, I21 to 8, 9, 10 if you want to set Multi - Accel/Decel time via P3-P5 terminals.
Multi-Accel/Decel time 0 is settable at ACC and dEC.
Multi-Accel/Decel time 1-7 is settable at I34-I47.
Accel/Decel
time
P5 P4 P3
0
-
-
-
1 - -
2 -
-
3
-
4
- -
5
-
6
-
7
Frequency
P3
P4
P5
FX
Accel
Time 0
Accel
time 1
Accel
time 2
Accel
time 3
Decel
time 4
Decel
time 5
Decel
time 6
Decel
time 7