EasyManua.ls Logo

SBC PCD1.Room - Digital Inputs and Outputs (Terminal Block X0)

SBC PCD1.Room
95 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware Manual PCD1.M2110R1 │ Document 27-619 │ Version ENG 04 │ 2018-08-20
Saia-Burgess Controls AG
On-board│DigitalI/Os
Inputs/Outputs (I/O)
4-5
4
4.1.4 DigitalInputsandOutputs(TerminalBlockX0)
The connections No. 7 to No. 10 on Terminal Block X0 can be used as either
inputsoroutputs.ThecongurationiscarriedoutintheDeviceCongurator.
Dependingontheconguration,thetechnicaldatacorrespondstothatofapurely
digital input or output:
Conguredasaninput:
Input type: Source operation, electrically connected
Input voltage: Typ. 24 VDC(15…30 VDC)
Input current: Typ. 3.6 mA at 24 VDC
Input delay: Typ. 3 ms
Surge protection: No
LEDs No
Connections Plug-in screw terminal block
Conguredasanoutput:
Short-circuit protection Yes
Voltage range 24 VDC (12...32 VDC) smoothed
Output current Max. 0.5 A
Output delay Typ. 50 µs, max 100 µs at Ohmic load
LEDs No
Connections Plug-in screw terminal block
Uext
Uext
Uext
11
12
13
14
15
16
17
18
19
10
9
8
7
6
5
4
3
2
1
0
I2
I3
I1
I0
O0
O2
O3
O1
IO5
IO4
IO6
IO7
X0X1
Uext.
GND
IX0
IX1
AI0
AI1
-
+
-
24 VDC
3.6 mA
In7
Uext
Out7
In6
In5
In4
Out6
Out5
Out4
current Limit
PWO or
O8
digital
Inputs and outputs
NOTE:SubjectterminalblockX0
The terminal Uext serves to feed the outputs to terminals 7 ... 10th
If at least I / O 4 ... 7 operated as a receipt, the following must be considered:
IfthisexternalsupplyUextwhichoutputsthepowero󰀨andtheinputsI/O4...
7 is still tension on the supply voltage of the outputs O 0, ... 3 and I / O 4 ... 7 via
the built-in output transistor of the I / Os diode fed back and would feed the device
connected to the output load.