4.1.4 DigitalInputsandOutputs(TerminalBlockX0)
The connections No. 7 to No. 10 on Terminal Block X0 can be used as either
inputsoroutputs.ThecongurationiscarriedoutintheDeviceCongurator.
Dependingontheconguration,thetechnicaldatacorrespondstothatofapurely
digital input or output:
Conguredasaninput:
Input type: Source operation, electrically connected
Input voltage: Typ. 24 VDC(15…30 VDC)
Input current: Typ. 3.6 mA at 24 VDC
Input delay: Typ. 3 ms
Surge protection: No
LEDs No
Connections Plug-in screw terminal block
Conguredasanoutput:
Short-circuit protection Yes
Voltage range 24 VDC (12...32 VDC) smoothed
Output current Max. 0.5 A
Output delay Typ. 50 µs, max 100 µs at Ohmic load
LEDs No
Connections Plug-in screw terminal block
Uext
Uext
Uext
11
12
13
14
15
16
17
18
19
10
9
8
7
6
5
4
3
2
1
0
I2
I3
I1
I0
O0
O2
O3
O1
IO5
IO4
IO6
IO7
X0X1
Uext.
GND
IX0
IX1
AI0
AI1
-
+
-
24 VDC
3.6 mA
In7
Uext
Out7
In6
In5
In4
Out6
Out5
Out4
current Limit
PWO or
O8
digital
Inputs and outputs
NOTE:SubjectterminalblockX0
The terminal Uext serves to feed the outputs to terminals 7 ... 10th
If at least I / O 4 ... 7 operated as a receipt, the following must be considered:
IfthisexternalsupplyUextwhichoutputsthepoweroandtheinputsI/O4...
7 is still tension on the supply voltage of the outputs O 0, ... 3 and I / O 4 ... 7 via
the built-in output transistor of the I / Os diode fed back and would feed the device
connected to the output load.