Hardware Manual PCD1.M2110R1 │ Document 27-619 │ Version ENG 04 │ 2018-08-20
Saia-Burgess Controls AG Communications Interfaces
6
6-6
On-board│Port#1│SlotA
Malfunction
If interface modules of the PCD7.F1xxS series (hardware version A) are used
with the following devices, the interface modules will become hot and their correct
function cannot be guaranteed.
- PCD1.M1xx
- PCD2.M1xx
- PCD2.M48x
- PCS
The hardware version can be seen on the white label of a PCD7.F1xxS module in
the middle text line.
Solution
Only use PCD7.F1xxS interface modules PCD7.F1xxS with hardware version B
or newer. These are suitable for all PCD generations.