even if the drop is very short (30ms).
In case multiple inputs are in alert state, only the alert which appeared first is shown.
0 = OK , “3” means that there was an input/line/phase voltage alert at phase 3
outlet current drop
alert
(1)
Outlet drop alert raised for outlet number ..n.. .
In case multiple outlets are in alert state, the highest outlet will be indicated.
0 = OK , “22” means that there was a current drop at outlet “22”
input current drop
alert
(1)
Input current drop alert raises due to a sudden current drop for an input. In case multiple inputs are
in alert state, the highest input will be indicated.
‘0’ is the indication of everything's all right.
Sensor change alert raises when a sensor type has been changed. If multiple sensor types have
been changed the lowest sensor channel will be shown.
‘0’ is the indication of everything's all right.
outlet voltage drop
alert
(1)
Outlet voltage drop alert raises for outlet number ..n.. .
In case multiple outlets are in alert state, the highest outlet will be indicated.
The threshold is hard coded on 118V.
0 = OK , “22” means that there was a current drop at outlet “22”
(1) Only the first alert is flagged
Input overcurrent thresholds can be changed at the < Inputs > tab
Outlet overcurrent thresholds can be changed at the < Outlets > tab
General alert setting can be changed at the < System > tab
V252_User manual
Schleifenbauer PDU