Manual – DFE32B Fieldbus Interface PROFINET IO
123
10
Diagnostics procedures
Error Diagnostics
Diagnostic problem 1: Inverter does not work on PROFINET IO.
Initial status:
Inverter is connected to PROFINET IO
Inverter configured in IO controller and bus communication is active
Is the bus connector plugged in? No [A]
Yes
Yes
Response of the Link
LED?
OFF ? [C]
Response of the
BUS FAULT LED?
Yellow
Red
[B]
[C]
Green
Off
Inverter has no connection to Ethernet
Compare set PROFINET name to project planning.
PROFINET names identical? No [D]
Yes
You may have performed the project planning for an incorrect unit type or defined an
incorrect configuration.
Delete project planning for the inverter from the PROFINET IO network.
Reconfigure the inverter again, choosing the unit designation "MDX61B+DFE32B".
Assign the address range for your control system.
Load the project planning data into the PROFIBUS IO controller master and restart the
bus communication.
[A] Check the bus cabling.
[B] The DFE32B option was not yet configured or configured incorrectly.
Check the project planning, particularly the device name and the IP
address.
[C] The DFE32B option indicates that the PROFINET IO controller has not
yet established communication.
The PROFINET IO controller is switched off or has not yet been
started up.
[D] Adapt PROFINET names