24
Manual – DFE32B Fieldbus Interface PROFINET IO
4
Setting the IP address parameters via DCP
Assembly and Installation Notes
4.8 Setting the IP address parameters via DCP
Initial startup For PROFINET IO, the IP address parameters are determined via the "DCP" protocol
(Discovery and Configuration Protocol). DCP operates with device names. The device
name uniquely identifies a PROFINET IO node in the network. It is identified with the
PROFINET IO controller for the project planning of the node and also set using the proj-
ect planning software on the PROFINET IO device. With the aid of the device name, the
controller identifies the device during startup and transfers the corresponding IP address
parameters. Settings directly on the slave are no longer required. The basic procedure
is described with SIMATIC STEP 7 as an example in section "Project Planning with
PROFINET" (→ subsection "Assigning the PROFINET device name").
Resetting the IP
address parame-
ters
If you do not know the IP address parameters and cannot access the inverter using the
serial interface or the DBG60B keypad, you can reset the IP address parameters to the
default values using the DIP switch "Def IP".
This action resets the DFE32B option to the following default values:
• IP address: 192.168.10.4
• Subnet mask: 255.255.255.0
• Default gateway: 1.0.0.0
• PROFINET device name: PNETDeviceName_MACID
Proceed as follows to reset the IP address parameters to the default values:
• Switch off the 24 V DC supply voltage and the mains voltage.
• Set the DIP switch "Def IP" on the DFE32B option to "1".
• Switch the DC 24 V supply voltage and the line voltage back on.
• Wait until the DFE32B option boots up. This is indicated by the green "Run" LED.
You can now access the inverter via the IP address 192.168.10.4. Proceed as follows
to set new IP address parameters:
• Start a web browser and access the homepage of the DFE32B option or start
MOVITOOLS
®
MotionStudio.
• Select the required address parameters.
• Set the DIP switch "Def IP" on the DFE32B option to "0".
• The new address parameters are adopted after the device is switched off and
switched on again.