Manual – DFE32B Fieldbus Interface PROFINET IO 
15
4
Installing the DFE32B option card in MOVIDRIVE® B
Assembly and Installation Notes
4.2 Installing the DFE32B option card in MOVIDRIVE
®
 B
4.2.1 Connecting a system bus (SBus 1) between a MOVITRAC
®
 B and the DFE32B option
To simplify cabling, the DFE32B option can be supplied with DC 24 V from X46.7 of the
MOVITRAC
®
 B to X26.7.
MOVITRAC
®
 B must be supplied with DC 24 V at terminals X12.8 and X12.9 when it
supplies the DFE32B option.
Activate the system bus terminating resistor at the FSC11B option (S1 = ON).
INFORMATION
•MOVITRAC
®
 B does not require a special firmware status.
• Only SEW-EURODRIVE personnel may install or remove options cards for
MOVITRAC
®
 B.
61633AXX
X46 X26 Terminal assignment
X46:1 X26:1 SC11 SBus +, CAN high
X46:2 X26:2 SC12 SBus -, CAN low
X46:3 X26:3 GND, CAN GND
X46:7 X26:7 DC 24 V
X12 Terminal assignment
X12:8 DC+24 V input
X12:9 GND reference potential for binary inputs
X45
X46
1
23456HL ⊥
FSC11B
S1
OFF
ON
7
S2
X44
X26
1234567
X24
H1
H2
X12
1
2
3
4
5
6
7
8
24V IO
DC 24 V
–
+
9
GND
=
DFE 32B
X30X32
Def IP
PROFINET IO
AS
RUN
BUS
FAULT
01