126
Manual – DFE32B Fieldbus Interface PROFINET IO
11
DFE32B for MOVIDRIVE® B, MOVITRAC® B and UOH11B
Technical Data
11 Technical Data
11.1 DFE32B for MOVIDRIVE
®
B, MOVITRAC
®
B and UOH11B
DFE32B option
Part number 1821 345 6
Power consumption P = 3 W
Voltage supply (only in
gateway operation)
U = DC 24 V (-15%/+20%)
I
max
= DC 200 mA
P
max
= 3.4 W
Application protocols • PROFINET IO (Ethernet frames with frame identification 8892
hex
) to con-
trol and parameterize the inverter.
• HTTP (Hypertext Transfer Protocol) for diagnostics using a Web browser.
• SMLP (Simple Movilink Protocol), protocol used by MOVITOOLS
®
.
Port numbers used • 300 (SMLP)
• 80 (HTTP)
Ethernet services •ARP
• ICMP (ping)
ISO/OSI layer 2 Ethernet II
Baud rate 100 MBd in full duplex mode
Connection technology RJ45
Addressing 4 byte IP address or MAC-ID (00:0F:69:xx:xx:xx)
Manufacturer ID
(Vendor ID)
010A
hex
Tools for startup • MOVITOOLS
®
MotionStudio version 5.40 and higher.
• DBG60B keypad
Firmware status of
MOVIDRIVE
®
MDX61B
Firmware version 824 854 0.17 or later (→ display with P076)