18
Manual – DFE32B Fieldbus Interface PROFINET IO
4
Installing the DFE32B/UOH11B gateway
Assembly and Installation Notes
4.3 Installing the DFE32B/UOH11B gateway
The following figure shows the connection of the DFE32B option via the UOH11B:X26
gateway housing.
The gateway housing is powered with DC 24 V at X26.
Connect the system bus terminating resistor at the end of the system bus connection.
INFORMATION
Only SEW-EURODRIVE engineers are allowed to install or remove option cards
in/from the UOH11B gateway housing.
61636AXX
UOH11B gateway housing
X26 Terminal assignment
X26:1 SC11 system bus +, CAN high
X26:2 SC12 system bus -, CAN low
X26:3 GND, CAN GND
X26:4 Reserved
X26:5 Reserved
X26:6 GND, CAN GND
X26:7 DC 24 V
X26
1
23456
7
SEW Drive
UOH11B
DC+24 V
GND
X24
H1
H2
SC11 Systembus +, CAN high
SC12 Systembus -, CAN low
GND, CAN GND
DFE 32B
X30X32
Def IP
PROFINET IO
AS
RUN
BUS
FAULT
01

Table of Contents