Manual – DFE32B Fieldbus Interface PROFINET IO
35
5
Project planning for the PROFINET IO controller
Project Planning with PROFINET
Starting the con-
troller
Load the project planning in the SIMATIC S7 and start the module. The Error LED of the
controller should now go out.
The LEDs of the DFE32B option should have the following statuses:
• RUN LED: lights up green
• BUS FAULT LED: off
• Link/Activity LED: Flickering
If this is not the case, check the project planning, especially the device name and the IP
address of the node.
Project planning
example for the
process data con-
figuration of
MOVIDRIVE
®
B
This example is to show the positioning of the drive via MOVIDRIVE
®
B. The "Extended
positioning via bus" application module can be used.
The information between PLC and inverter is exchanged via 6 process data words.
The following figure shows the corresponding PROFINET parameterization.
62347AEN
68073AEN
Status –
Wort
Ist –
position
Ist –
position
Ist –
drehzahl
Ausgangs –
strom
Geräte –
auslastung
6 process input data
Status –
Wort
Ist –
position
Ist –
position
Ist –
drehzahl
Ausgangs –
strom
Geräte –
auslastung
Status –
Wort
Ist –
position
Ist –
position
Status
word
Actual
position
Actual
position
Ist –
drehzahl
Ausgangs –
strom
Geräte –
auslastung
Actual
speed
Output
–
current
Unit
utilization
De -
celeration
Beschleu-
nigung
Soll-
drehzahl
Ziel-
position
Ziel-
position
Control
Wort
6 process output data
- Beschleu-
nigung
Soll-
drehzahl
Ziel-
position
Ziel-
position
Control
Wort
Beschleu-
nigung
Soll-
drehzahl
Accelera -
tion
Setpoint
speed
Ziel-
position
T-
position
Control
Wort
Target
position
Target
position
Control
word
Outputs
Inputs
IO controller:
e.g. PLC
IO device:
e.g. drive inverter